Does CHANCE make temporary grounding sets for specific system voltages?

CHANCE provides a wide range of protective grounding products to address nearly every temporary grounding situation. A properly rated temporary grounding set is determined by the maximum possible fault current at the grounding location and not the system voltage.  The information needed to properly specify a ground set includes maximum available fault current, level of asymmetry of the fault current (X/R), duration of the fault current, length of grounding cables needed, and the type and size of clamps needed.