Does CHANCE® make a Fuse Link specifically for Transformer Protection?

Yes. The SloFast Fuse Link is designed specifically for transformer protection. The reason it is well suited for transformer protection is that the Time Current Curve of the SloFast fuse link more closely matches the transformer safe loading curve than the Time Current Curves of other types of fuse links. The SloFast fuse link has a dual element design and this unique design allows the end user to get full use of the transformers capability without subjecting it to damaging overloads for extended periods of time.