Can I use a 27kV 150 kV BIL cutout on a 34.5 kV system? ← Switching & Fusing Yes, but only if the system is single-phase to neutral or three-phase solidly-grounded wye, where the TRV does not exceed the maximum design voltage of 27 kV.